Your Commissioning Report, Explained
Here are readings from real South Bay systems, with every number on the HVAC commissioning report translated into plain English. One passed. One did not. By the end of this page you will be able to read your own HVAC commissioning report without anyone interpreting it for you.
A system that came back healthy
An R-410A split system on a San Jose home, measured after fifteen minutes of runtime so the readings had settled.
| Reading | Measured | What it means in English |
|---|---|---|
| Return air, dry bulb | 70.9 °F | The temperature of the air the system is pulling out of your house. |
| Supply air, dry bulb | 53.8 °F | The temperature of the air it is blowing back out of the registers. |
| Temperature split | 17.1 °F | The difference between those two. This is the headline number. Healthy is roughly 16 to 22 degrees. This one is comfortably in range. |
| Return air, wet bulb | 60.9 °F | Temperature accounting for humidity. It is what sets the correct charging target for the day, which is why charging by pressure alone does not work. |
| Suction pressure | 125.6 PSIG | Low side pressure, which converts to a 43.0 °F saturation temperature. Cold enough to pull heat out of the air without freezing the coil. |
| Liquid pressure | 317.6 PSIG | High side pressure, converting to 99.9 °F. This is where the heat is being dumped outside. |
Readings taken with the system running under real load, not at startup. A system measured cold reports numbers that mean nothing.
Why the split matters more than the vent feeling cold. Air from a register always feels cold against your skin, even from a system delivering half its rated capacity. Seventeen degrees of split across a known airflow is arithmetic, and arithmetic does not have an opinion.
A system that looked fine and was not
Same city, different house, an R-453A system on an 86 degree afternoon. The homeowner’s complaint was that it ran constantly and never quite cooled the house. Here is why.
| Reading | Measured | What it means in English |
|---|---|---|
| Airflow | 1,600 CFM | The blower was moving plenty of air. That is the airflow a four ton system expects, so the blower was not the problem. |
| Temperature split | 7.1 °F | The problem. Should be 16 to 22. At seven degrees the system is barely changing the air it moves. |
| Superheat | 21.4 °F | High. Superheat this far up means not enough refrigerant is reaching the evaporator coil, so much of the coil is doing no work. |
| Condenser status | Starved | The outdoor unit was not getting the refrigerant it needed, with only 7.0 degrees of temperature difference over ambient where it should be far higher. |
| Total capacity delivered | 23,195 BTU | The number that ends the argument. Set up to move four tons of air, delivering under two tons of cooling. Roughly half. |
| Sensible capacity | 12,409 BTU | The portion actually lowering air temperature. The rest was spent pulling moisture out. |
| Faults flagged | 24 | The system reported two dozen individual faults, which together pointed at one cause rather than twenty four separate repairs. |
Nothing in that house looked broken. The condenser ran, the blower ran, and cold air came out of every register. Without measuring capacity, the honest diagnosis available to anyone was “seems to be working, maybe it is undersized,” and the usual next step is quoting a bigger system. The bigger system would have had the same problem.
What a pass actually looks like
The two examples above are diagnostic visits on systems somebody else installed. This one is the other end of the job: a line set being evacuated before the refrigerant goes in.
Why this graph matters more than it looks
Air and moisture left inside a system do not burn off. They combine with refrigerant and oil to form acid, and that acid is what eats a compressor from the inside years later. The only way to get them out is to pull the system into a deep vacuum and prove it holds.
The industry standard is 500 microns. This job finished at 278.7 and the decay test held, which is why the trace flattens along the bottom instead of climbing back up. A system that cannot hold vacuum has a leak, and charging it anyway just buries the problem.
Two and a half hours of that clock is the part that gets skipped. It is unbillable, invisible, and it is the single biggest predictor of whether the compressor is still alive in year twelve.
The four HVAC commissioning report numbers that matter most
Report formats differ between contractors. These four readings appear on all of them, and together they answer almost every question worth asking.
Temperature split
Return air temperature minus supply air temperature. Too low means low capacity, low airflow or low charge. Too high usually means the blower is not moving enough air across the coil.
Total external static pressure
How hard the blower fights the duct system. Above 0.5 and the equipment cannot deliver its rated airflow, which caps every other number on the page.
Superheat and subcooling
The two charge readings. Superheat matters most on fixed orifice systems, subcooling on TXV systems. The correct target changes with outdoor temperature and indoor humidity, so a number without its target means nothing.
Delivered capacity in BTU
The bottom line. One ton equals 12,000 BTU, so a three ton system should be delivering somewhere near 36,000 under design conditions. This is the number that tells you whether you got what you paid for.
What the flags on your HVAC commissioning report mean
Faults are ranked, because twenty four small faults usually add up to one real problem rather than twenty four repairs.
Critical. Can lead to system or compressor failure if left unresolved. Needs attention now.
Several minor faults that in combination indicate a larger system wide issue.
Minor faults that are contributing factors to the bigger ones.
No faults detected. The system is performing as designed.
A flag is a symptom, not a sentence. The job is to work out which single underlying condition is producing them, fix that, and re run the test to confirm the flags clear. Clearing a fault in the software does not fix anything in your house, and any report that shows faults cleared without a corresponding repair should be questioned.
Using Your Commissioning Report After The Visit
A commissioning report is not a receipt to file and forget. It is the baseline for every service visit after it. The day a system starts acting up, the fastest diagnosis is comparing today against the day it was right. If the static pressure climbed from 0.48 to 0.75 inches, something changed in the airflow: a filter, a closed register, a collapsed duct. If subcooling dropped while superheat climbed, that points at charge. Without the original commissioning report, a tech starts from zero and has to guess what normal looked like for your house.
Keep a copy with the equipment manual, and keep a digital copy where you can find it. Hand it to anyone who services the system, even if it is not us. A good tech will be glad to have it.
Reading The Commissioning Report Over Several Years
One report is a snapshot. Two or three are a trend, and trends catch problems early. A slow drift in subcooling over three seasons usually means a small leak. A temperature split that shrinks every year often means a coil loading up with dirt on the air side. Rising static pressure with the same filter type points at the ducts or the coil. None of those show up as a fault code until they are already expensive.
Run the same tests under similar conditions when you can. Readings taken on a 95 degree afternoon and a 70 degree morning will not match, and that is expected. The software corrects for indoor and outdoor conditions, which is exactly why the targets on the report move from visit to visit while the system itself has not changed.
What A Commissioning Report Will Not Tell You
The commissioning report measures how the system is running right now. It does not see inside a heat exchanger, predict when a motor bearing will go, or tell you whether the ductwork in the attic is crushed in a spot nobody can reach. It will often show the symptom of those things, like a static pressure jump or a weak temperature rise, but finding the cause still takes eyes and hands.
It also only reports what was measured. A report with three numbers on it is not the same as a report with twelve. If airflow was not measured, the charge readings on that page rest on an assumption. When you read any commissioning report, look for what is missing as much as what is there.
Questions Worth Asking About Any Commissioning Report
Was static pressure measured at the equipment, and what is the rated maximum? Was the charge confirmed with superheat or subcooling, and which one does this equipment call for? What was the delivered capacity compared to the rating? If anything is flagged, what single condition explains it, and what does the fix involve? A contractor who took the readings will answer all four in plain English. If the answers are vague, the readings probably were too.
Heat Pumps, Furnaces, And The Winter Version Of The Report
Cooling season gets most of the attention, but heating equipment gets a commissioning report too. A heat pump in heating mode is measured the same way with the roles reversed: the indoor coil becomes the condenser, so the readings and targets flip. Delivered heating capacity, supply air temperature, and defrost behavior all matter, and a heat pump that cools fine can still be undercharged for heating.
Gas furnaces get a different set of numbers. Temperature rise across the heat exchanger gets compared to the range printed on the furnace label. Gas manifold pressure gets set to the rating plate. Static pressure still matters, because a furnace starved for air runs its heat exchanger hot, trips its high limit, and wears out early. Combustion and carbon monoxide readings round it out. Same idea as the cooling report: measure, compare to the target, and write it down so the next visit has something to compare against.
When The Commissioning Report Says Something Is Off
A flagged reading is the start of a conversation, not the end of one. The right response is to find the one condition that explains the flags, fix it, and run the test again to show the flags cleared. Sometimes that is a five minute blower speed change. Sometimes it is a duct modification that needs its own quote. Either way, you should see a second set of numbers after the fix, on the same commissioning report format, so you can compare before and after yourself instead of taking anyone’s word for it.
If you have an older report from another company, bring it out. Even a partial set of readings from a few years ago is a useful comparison. A system whose subcooling or static pressure has moved since then is telling a story, and a new commissioning report placed next to the old one often explains a comfort problem faster than any single visit could on its own.
Common questions
My split is 14 degrees. Is my system broken?
Not necessarily, and this is exactly why single readings are misleading. A 14 degree split on a very humid day can be normal, because the system is spending capacity removing moisture instead of lowering temperature. The same 14 degrees on a dry 95 degree afternoon is a real problem. The target moves with conditions, which is why a report should always show the target next to the reading.
Why does the report show pressures and temperatures for the same thing?
Refrigerant pressure and temperature are locked together while liquid and vapour coexist, so 125.6 PSIG of R-410A is always 43.0 degrees. Technicians read pressure because it is easy to measure, then convert to temperature because temperature is what actually does the work.
Do I get a copy?
Yes, and it is yours permanently. Keep it. If you sell the house it is genuine documentation, and if another technician works on the system it saves them an hour of guessing at what normal looks like for your equipment.
What if my contractor will not give me the numbers?
Then most likely there are no numbers, because a technician who took readings has them on a phone and can send them in about a minute. That is not always bad faith. It is usually just how the visit was priced and scheduled.
Keep reading
Where the HVAC commissioning report targets come from
We did not invent the numbers on this page. The targets behind these HVAC commissioning report checks are published by the bodies below, and you can read them yourself without going through us.
Get a report on your own system
The residential diagnostic is $99, credited toward the repair when you approve it on the same visit.